To control the OpcUa-Client node, pass a message with specific properties. The msg.topic defines the target NodeId and DataType in the format ns=3;s=Counter;datatype=Int32. The msg.action determines the operation to perform.
### Input Message Properties
| Property | Function/Value | Notes |
| :--- | :--- | :--- |
| payload | set interval for subscription or monitorItem | |
| interval | Subscription interval | |
| queueSize | Subscription queue size | |
| deadbandType | "a" abs. or "p" percent | Action monitor |
| deadbandValue | integer for deadband | Action monitor |
| topic | NodeId and DataType in format `ns=3;s=Counter;datatype=Int32` | |
| action | subscribe | nodeId / variable |
| | unsubscribe | nodeId / variable |
| | deletesubscription | subscription |
| | browse | nodeId / folder |
| | info | nodeId |
| | read | nodeId |
| | write | nodeId & value |
| | monitor | deadbandtype abs/pro |
| | events | nodeId |
| | readmultiple | [nodeId + datatype] |
| | writemultiple | [nodeId + datatype + value] |
| | clearitems | empty multiple items (readmultiple / writemultiple) |